In addition to the discharge current, the lightning protection capability also depends on the test waveform. The outdoor incoming cabinet uses a Class 1 surge protector, and the lightning current waveform is (10/350μs). According to the highest protection standard (explosive environment), the total lightning The current is only 200KA. The biggest risk to the power distribution system is that each line flows through 25KA. For the base station, even if it is designed according to Category 2, the discharge current of each line is 20KA, which meets the protection requirements. The largest 100kA, 200kA, 400kA (8/20μs) products on the market use varistors and diodes that can only be used as Class 2 surge protectors and cannot pass the Class 1 test, which means they cannot be used for outdoor incoming lines The protection of the cabinet, and the maximum discharge current claimed by such products is 100kA, 200kA, 400kA (8/20μs), which is realized by multiple discharge devices in parallel. action and burn. Furthermore, the meaning of the maximum surge protection capability is that it will be damaged after one hit, which cannot be used as the main parameter in the standard.
The leakage current test is an important item in the detection of industrial surge protectors. According to the technical specifications, the test requirements are listed as follows:
(1) The test is only applicable to SPDs with metal oxide varistor (MOV) as the voltage limiting element and no other series-parallel elements.
(2) The leakage current value of the SPD can be measured with a lightning protection component tester or a leakage current test meter.
(3) First, disconnect the backup protection device and confirm that the power supply is disconnected, then directly measure the corresponding module with the instrument, or remove the pluggable SPD from the line for measurement.
(4) Qualification judgment basis: When measuring 1ma for the first time, the measured value of the leakage current of the SPD composed of a single MOV should not exceed the nominal maximum value of the manufacturer; if the leakage current is not declared by the manufacturer, the measured value should not be greater than 20μA. For a surge protector with multiple MOVs connected in parallel, the measured leakage current should not exceed the maximum nominal value of the manufacturer. If the manufacturer declares the leakage current, the measured value should not be greater than 20μA multiplied by the number of MOV valves. When the number of valves cannot be determined, the measured value of the surge protector should not be greater than 20μA.
(5) When the subsequent measurement is 1ma, the measured value of the leakage current of the surge protector composed of a single MOV and multiple MOVs should not be greater than 1 times the first measured value.
Do every inverter has a surge protector? Where to install the surge protector in the PV system?June 5, 2025Inverter is indispensable in a PV system. But not every inverter is equipped with a surge protector. Some newer and more advanced inverter models have built-in surge protection as a standard feature, ...view
Do surge protectors work against lightning?April 27, 2025Although surge protectors cannot directly prevent lightning strikes, they can significantly reduce the damage caused by lightning strikes to electrical equipment and circuits. As a specially designed ...view
Maximizing Equipment Lifespan: Power Surge Monitoring for Industrial ApplicationsSeptember 11, 2023In industrial settings, where complex machinery and electronic equipment are the backbone of operations, ensuring the longevity and reliability of these assets is of paramount importance. Industrial e...view
Protect Your Surveillance: The Importance of Surge Protectors for CCTV CamerasJune 6, 2024In today's world, ensuring the safety and security of your property is more crucial than ever. Closed-circuit television (CCTV) cameras have become an essential tool in monitoring and safeguarding...view
PC power supplies have built-in surge protection or not ? TECHWIN provides indispensable protectionMay 8, 2025PC power supplies (PSUs) typically include basic surge protection, but they are not designed to handle large power surges (e.g., lightning strikes or grid fluctuations) effectively. Here’s how Shenzh...view
Difference Between Surge Protector and Backup ProtectorApril 26, 2022The special protection device for low-voltage surge protector (SSD) is an external disengagement device of the surge protector used in the low-voltage power supply system, which can withstand the expe...view