The position of the surge protector: the surge protector is an important component of the lightning protection project in a building, so the location of the surge protector is very important for the entire lightning protection project. The determination of the installation location of the surge protector against lightning needs to involve a lot of things. Next, Techwin will analyze the determination of the installation location of the surge protector.
Level configuration ininstalling surge protection device: incorrect level configuration often results in waste or even failure of the surge protector against lightning. Key points and principles of level configuration: first, it should be set at the junction of any two lightning protection zones, and then whether the power line in the same lightning protection zone is too long and whether it is needed to add another level in this zone should be considered.
A low-voltage surge protector should be configured on the low-voltage side of the transformer supplying power to the building. If the distance between the transformer and the main distribution cabinet is less than 20m, this surge protector can be combined with the first-level surge protector inside the building. Low-voltage side surge protectors require a decentralized multi-stage configuration. The first-level protection is installed between the LPZ0 and LPZ1 areas of the lightning strike area and is installed in front of the distribution box of the main power incoming line. The maximum discharge current is 80KA (10/350μs), and the action time is less than 100ns. Its main function is to release the energy of direct lightning strikes. In terms of the second level of protection, between zone 0 and zone 1 of the lightning strike area, the spd for lightning protection is installed in front of the UPS or distribution box. The maximum discharge current is 40KA (8/20μs), and the action time is less than 25ns. Its main function is to limit the voltage amplitude of the induced overvoltage.
Techwin products are widely used in communication, electric power, finance, railway, transportation, petrochemical, security monitoring, meteorology and photovoltaic, wind power, and new energy industries. At present, the company has passed ISO9001, CE, ROHS, CQC Golden Sun, and many other authoritative certifications in the international market. So far, it has been successfully applied to China Mobile, China Unicom, Beijing Olympic Games, Shanghai World Expo, Shenzhen Universiade, Southern Xinjiang Railway, Guangzhou Baiyun Airport, and many other major projects.
Choosing the Right Power Surge Monitoring Device for Your HomeSeptember 11, 2023In an era where our homes are filled with a multitude of electronic devices, ensuring their safety and longevity is paramount. Power surges, often caused by electrical fluctuations or lightning strike...view
Choosing and Applying AC SPDJuly 3, 2024With the continuous development of modern power systems, AC surge protection devices (SPD) are playing an increasingly important role in power systems. AC SPD can effectively protect electrical system...view
Surge Protector Safety TipsFebruary 29, 2024When it comes to protecting your electronics from harmful power surges, surge protectors are an essential tool. These devices help regulate the flow of electricity to your devices, preventing damage f...view
Signal Surge Protector: Safeguarding Electronic Systems Against LightningDecember 12, 2024The surge protector is an electronic device that provides safety protection for various electronic equipment, instruments, and communication lines. According to its use, it can be divided into power s...view
The Difference Between Surge Protector and Air SwitchJuly 8, 2022Air switches and surge protectors are usually installed in the distribution box of a building, so what is the difference between them? Tiandun Thunderbolt will do a detailed analysis for you.Ⅰ. Surge...view
Lightning Protection Scheme for Drone Ground Control Station - Focus on SPD ConfigurationOctober 31, 20251.Core Principle: Zoning and Staged ProtectionThe Ground Control Station (GCS)—whether a fixed building, shelter, or vehicle—must be treated as a system requiring multi-layered protection. Adhering ...view